Diesel consumption and generator set range

Enter the power, how many hours the generator spends in each load band, and the tank. The page calculates the average consumption, the consumption per kWh, how many hours the tank lasts, and the tank size needed for the required autonomy.

Pre-sizing and estimating tool: the results do not replace a design, calculation, or report signed by a qualified professional, nor verification against the applicable standards.

VerificationRevision 12/11/2026

Technical responsibility. This calculator is under verification. The reference values and examples are hypothetical, to illustrate the calculation, and are not technical references. The user is responsible for the data entered, the choice of parameters, and the use of the results, and must validate them with a qualified professional before any decision, purchase, application, or construction work.

Generator set
Load profile

Hours in each band over a typical operating period (one day, one power outage, or one shift).

Consumption curve

Example values for a 500 kVA group in continuous duty (prime). Replace with the figures from your equipment catalog.

Tank and range
Cost
Top-up: farm machinery

The diesel price is the same field as in the generator section above. The default values are hypothetical, only to illustrate the calculation, and are not technical references. Use the manufacturer's consumption or the consumption measured on your machine.

Data stays only in this browser and is not sent. Uncheck to erase it.

—Range with the tank, for the profile entered
—

Intake and specific consumption by load

Lines: liters per hour from the curve in use and from the published linear model. Points: consumption per kWh.

Tap the chart to see the values.

Tank range at constant load

Operating hours with the tank's usable volume, if the generator always ran at the same load. The dashed line is the desired autonomy.

Tap the chart to see the values.

What if the data changes?

Drag the controls to simulate data different from what you entered (from 30% less to 30% more) and watch the result change instantly.

Tap the chart to see the values.

Tank range according to the generator load

Consumption, specific consumption and tank range for loads of 25% to 100% of rated power.

Step by step with your numbers

The calculation done in steps, with the values you entered.

    —Diesel consumption per hour of farm machinery
    —

    Liters per hour by load factor

    Hourly consumption for load factors of 40% to 100%; the highlighted bar is your load.

    Tap the chart to see the values.

    Diesel per hectare by yield

    Diesel cost per hectare for outputs of 6 to 16 ha/h; the highlighted bar is your output.

    Tap the chart to see the values.

    The calculation memo gathers this page's inputs, results, equations, assumptions, and references, with fields for project, responsible person, and review. The full report also includes the charts and interpretations, in color. In the print window, choose Save as PDF.

    How to use

    The page has two parts. The first, generator set consumption and autonomy, calculates the generator's fuel use from the catalog load curve (or the manufacturer's coefficients), the diesel for the period, the tank range, and the cost per hour and per kWh. The second, Top-up: farm machinery, calculates the hourly fuel use of a tractor, combine or pump engine from power, load factor and specific fuel consumption, and the diesel per hectare based on the operating rate.

    The diesel price is a single field, in the first part, and applies to both.

    Hypothetical example (illustrative values)

    Hypothetical values, to understand the calculation. They are not technical or market references.

    Farm machine: 120 kW engine working at 70% of power, with a specific consumption of 0.22 L/kWh. Consumption is 120 × 0.70 × 0.22 = 18.48 L/h. At a rate of 12 ha/h, it is 18.48 ÷ 12 = 1.54 L/ha. At R$ 6.20 per litre, the diesel costs R$ 9.55 per hectare.

    Default example generator: 500 kVA with a power factor of 0,8, with a 24 h load profile. Average consumption is 69 L/h, with 106 L/h at full load. A 2,000 L tank with 90% usable lasts about 26 hours of autonomy at average consumption, and the fuel cost comes to about R$ 428 per hour.

    Precautions

    • Specific consumption and the load curve are reference values. Confirm with the manufacturer's manual or by measuring on your machine or generator.
    • For the total diesel for an area, see the passes and diesel by plot.
    • For the hourly cost of a machine, see the machine hourly cost.

    Method, assumptions, and references

    Equations used

    Top-up, hourly consumption: power × load factor × specific consumption (L/kWh)
    Top-up, diesel per hectare: (L/h ÷ output in ha/h) × diesel price
    P_nominal = kVA × PF; linear model: consumption(L/h) = a × P_nominal + b × P_delivered (a = 0.08145; b = 0.246 L/(h·kW))
    Manufacturer's curve: linear interpolation between 25%, 50%, 75% and 100%, extrapolated at the end segments
    Average consumption = Σ h_i·C(f_i) ÷ Σ h_i; specific consumption = Σ h_i·C(f_i) ÷ Σ h_i·f_i·P_nominal
    Range = V_tank × usable fraction ÷ average consumption; tank for t hours = consumption × t ÷ usable fraction

    Assumptions and limits

    • Diesel density of 0.84 kg/L and emission factor of 2.68 kg of CO₂ per liter.
    • The published linear model tends to overestimate the consumption of generator sets above 100 kVA; it serves as a conservative reference when there is no catalog.
    • Fuel cost only: maintenance, lubricating oil, ARLA 32 and depreciation are excluded. Altitude and temperature above the ISO 3046-1 conditions reduce the available power.
    • Emergency system standards usually require fuel for autonomy at full demand load; in that case, use the full-load autonomy.

    Standards and technical documents

    • ISO 8528-1: Reciprocating internal combustion engine driven alternating current generating sets — Application, ratings and performance
    • ISO 3046-1: Reciprocating internal combustion engines — Performance — Declarations of power, fuel and lubricating oil consumptions
    • Skarstein, Ø.; Uhlen, K. (1989): Design considerations with respect to long-term diesel saving in wind/diesel plants. Wind Engineering 13(2)
    • HOMER Energy: HOMER Pro user manual, generator fuel curve
    • NFPA 110: Standard for Emergency and Standby Power Systems

    Legislation and regulations in Brazil

    • ABNT NBR 17505: storage of flammable liquids and fuels
    • NR-20: occupational safety and health with flammable liquids and fuels
    • ANP Resolution No. 968/2024: specifications for diesel oils for Diesel-cycle engines
    • NR-10: safety in electrical installations and services

    Frequently asked questions

    How much diesel does a 500 kVA generator use?

    At full load (400 kW), a modern generator set uses close to 105 L/h; at 50%, about 57 L/h. The published linear model gives 131 L/h at full load, a more conservative figure.

    How to calculate the tank range?

    Divide the usable volume by the average consumption. A 2 000 L tank with 90% usable and an average consumption of 69 L/h lasts about 26 h.

    Why does consumption per kWh rise at low load?

    Part of the consumption happens even without load: friction, pumps and fan. At 25% load, a 400 kW set uses 0.34 L/kWh, versus 0.27 L/kWh at 75%.

    Which tank should I buy for 24 h?

    Multiply the average consumption by 24 and divide by the usable fraction: 69 L/h × 24 ÷ 0.9 = 1 840 L. If the standard requires full load, use 106 L/h: 2 830 L.